Model:VITD12/1600-31.5
Category:VI for indoor circuit breakers

| Main Technical Specification | ||
| VOLTAGE RATINGS | ||
| Rated voltage(Ur) | kV | 12 | 
| Rated short-time(1min)power-frequency withstand voltage(Ud) | kV | 48 | 
| Rated lightning impulse withstand voltage(Peak)(Up) | kV | 85 | 
| Rated frequency(fr) | Hz | 50 | 
| CURRENT RATINGS | ||
| Rated current(Ir) | A | 1250/1600 | 
| Circuit resistance at lowest rated contact force | μΩ | ≤20 | 
| Rated short-circuit breaking current(lsc) | kA | 31.5 | 
| Breaking operations of rated short circuit breaking current | Times | 30 | 
| Rated short-time withstand current(lk) | kA | 31.5 | 
| Rated duration of short-circuit(tk) | s | 4 | 
| Rated peak withstand current(lp) | kA | 80 | 
| Rated short-circuit making current(lMc) | kA | 80 | 
| Rated cable-charging breaking current(lc) | A | 25 | 
| Rated breaking current of single capacitor bank(lsb) | A | 400 | 
| Rated breaking current of back-to-back capacitor bank(lbb) | A | 400 | 
| MECHANICAL DATA | ||
| Weight of movable parts | kg | ≤1.3 | 
| Closing force due to bellow and atmosphere | N | 120±50 | 
| Force required to hold contacts open at full stroke | N | 190±60 | 
| MECHANICAL REQUIREMENTS | ||
| Clearance between open contacts | mm | 11±1 | 
| Average opening speed (contact close position~75%contact gap) | m/s | 1.0±0.25 | 
| Average closing speed (30%contact gap-contact close position) | m/s | 0.6±0.15 | 
| Rated added external contact final force | N | 3100±200 | 
| Added external contact force at contact touch point | 2200±150 | |
| Contact bouncing duration at closing operation | ms | ≤2 | 
| Closing and opening non-simultaneity of three-phase contacts | ms | ≤1 | 
| Maximum rebound during opening | mm | ≤3 | 
| LIFE | ||
| Storage life | years | 20 | 
| Rated mechanical endurance | Times | 10000 | 
| Contacts limit erosion | mm | 3 | 
Prev archive:Vacuum interrupter for indoor circuit breakerTD325Y